At a Glance
- HDOT Cx Outlets: Cx is the future-ready UL tested hybrid of a C13 and C19 outlet accommodating both C14 and C20 plugs.
- 45 Degree Angled Infeed: The angled infeed improves accessibility, provides infeed strain relief, and its bend radius is suitable with 60A rated cords.
- Network Monitoring: Gain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.
- Multi-Unit Linking & Cascading: Daisy chain up to 16 PDUs from a primary PDU using a USB or Ethernet connection through a single IP address.
- Multi-Color LCD: An easy-to-read LCD provides a local indication of power usage, alerts, and alarms.
- Hot Swappable Controller: The Controller is the PDU's center of intelligence and houses computing, display, and connectivity ports.
- Power Quality Measurements: Monitor and alert on the power being fed to the PDU for harmonics, voltage dips and swells, crest factor, and more at the outlet or load.
- RGB LED Outlet Indicators: RGB LEDs identify an outlet's on/off state, if it's above/below a certain power threshold, or if it's in suspect of a power measurement irregularity.
- Waveform Capture: Capture voltage and current waveforms automatically or upon demand.
- RamLock Locking Outlets: A mechanical locking mechanism built to secure the broadest range of C14 and C20 plugs in place.
- Environmental Monitoring: Support up to 12 daisy-chained DX2-series SmartSensors, each with the ability to send SNMP-based alerts and email notifications.
- Per-Inlet Power Sensing: PIPS® (Per Inlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, & Energy per inlet.
- Per-Outlet Power Sensing: POPS® (Per Outlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, and Energy per outlet.
- Branch Circuit Protection: This PDU meets the UL and IEC 62368-1 requirement for branch circuit protection through UL 489 rated magnetic-hydraulic circuit breakers or UL 248 fuses.
- Outlet Control: On Switched PDUs, cycle power to individual outlets or groups of outlets to reboot servers, or power off unused receptacles.
- Alternating-Phase Outlets: Evenly distributes multiple phases of power to each outlet for simplified load balancing, reduced cord lengths, and better airflow.
- High Temperature Rating: This product has been tested and approved for safe and reliable operation in 60 °C data center environments.
- Flexible Mounting: Includes standard button mounts along with provisions for custom mounting brackets.
- Color-Coded Options: Select from six colors to designate PDU circuits in the data center - black, white, red, green, blue, and yellow.
|
OverviewServer Technology's PRO4X Switched POPS PDUs run on our state-of-the-art Xerus network interface platform and provide remote access to power, PDU status, input, outlet and branch current monitoring, and outlet on/off control. The PDU features RamLock, a self-locking mechanism to prevent accidental cord disconnects, and our award-winning HDOT Cx outlets that can be deployed as either a C13 or C19. Switched POPS PDUs are secured with strong configurable password, active directory, 256-bit AES encryption, SSH, SSL and HTTPS support. SNMP traps provide automated alerts on power and environmental conditions from Legrand's plug-and-play environmental monitoring sensors like temperature, humidity, water, dry contact closure, airflow, air pressure differential, and more. |
Management- HTTP/HTTPS
- TLSv1.2
- SSHv2
- Telnet
- SNMPv2c
- v3 (GET, SET, Traps)
- IPv4 and IPv6
- LDAPv3/LDAPS
- TACACS+
- RADIUS
- FTP/SFTP
|
Certifications & StandardsNorth American: Safety (Listed & Certified, cTUVus mark) - UL 62368-1
- CSA C22.2 No. 62368-1
EMC - FCC Part 15 Subpart B Sections 15.107 & 15.109, Class A
- CANICES-003, Class A
Global: Safety - ENIEC 62368-1 (TUVR certified, T-mark)
- IEC 62368-1 incl. regional, national and harmonized differences (IECEE CB scheme) EMC
EMC - EN55032 / CISPR 32
- EN55035 / CISPR 35
- EN61000-3-2 / IEC 61000-3-2
- EN61000-3-3 / IEC 61000-3-3
CE Mark - 2011/65/EU (RoHS Directive)
- 2014/35/EU (Low Voltage Directive)
- 2014/30/EU (EMC Directive)
UKCA Mark - Electrical Equipment (Safety)
- Electromagnetic Compatibility
|
Package Contents- PRO4X 48-Outlets PDU
- Standard Button Mounts
|
Product Name | Switched Pops PRO4X IX PDU Wye 20A IEC 60309 3P+N+G 6 Hour Plug |
Manufacturer Part Number | C4G48RA-GNBD2FD3 |
Product Type | PDU |
Receptacle Type | IEC 60320 C13 CX |
Product Family | PRO4X |
PDU Type | Switched |
Remote Outlet Switching | Yes |
Locking Receptacles | RamLock Locking Outlet |
Receptacle Detail | 24 x IEC 60320 C13 24 x CX |
Environmental Compliance | Restriction of Hazardous Substances (RoHS) |
Plug / Connector Type | IEC 60309 3P+N+G 6Hr |
Features | Multi-color LCD |
Input Current | 20 A |
Mount Type | Button Mount |
Protection Type | Branch Circuit Circuit Protection Fuse |
Input Voltage | 415 V AC 230 V AC |
Output Voltage | 208 V AC 230 V AC |
Input Frequency | 60 Hz |
Minimum Operating Temperature | 32°F (0°C) |
Maximum Operating Temperature | 140°F (60°C) |
Minimum Storage Temperature | -22°F (-30°C) |
Maximum Storage Temperature | 176°F (80°C) |
Network (RJ-45) | Yes |
Load Capacity (Watt) | 11.50 kW |
Height | 80" |
Width | 2.2" |
Depth | 2.5" |
Product Series | PRO4X |
Application / Usage | Data Center |
Limited Warranty | 2 Year |
Circuit Breaker | Yes |
|