Altronix ACMS12/ACMS12CB are sub-assemblies designed to be used in Altronix wall and rack mount enclosures. Dual input design allows power to be steered from two (2) independent low voltage 5 to 24VDC power sources into twelve (12) independently controlled fuse or PTC protected outputs. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. ACMS12/ACMS12CB will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in Fail-Safe or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the twelve (12) outputs. The spade connectors allow you to daisy chain power to multiple ACMS12/ACMS12CB modules. This feature allows you to distribute the power over more outputs for larger systems.