The Altronix FireSwitch108 is a cost effective managed NAC Power Extender. It interfaces with 12 or 24VDC Fire Alarm Control Panels (FACP) to provide Notification Appliance Circuit expansion support, for additional horns/strobes to allow ADA compliancy. It also provides auxiliary power to support system accessories. It delivers electronically regulated and filtered 24VDC power to Class B or Class ANAC loop circuits. Additionally, a separate 1 amp auxiliary output for 4-wire smoke detectors is available. Alarm current can be divided between the eight (8) outputs for powering NAC devices. Outputs are rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals [NC, C, NO] which are used to indicate general loop/system trouble. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the eight (8) outputs. It provides a programmable LCD display interface, plus an ethernet port interface for remote programmability and monitoring.
Certifications & Standards
UL
CAN/ULC-S527-99 Control units for Fire Alarm Systems
CSFM
NFPA 72 Compliant
Miscellaneous
Input:
Power input: 120VAC 60Hz, 4.8 amp.
Two (2) Class A or two (2) Class B FACP inputs.
Two (2) configurable inputs trigger via Class A or Class B FACP signal circuits(polarity reversal) or dry contacts.
Output:
24VDC voltage regulated power-limited NAC outputs.
Output power:
10 amp max. total alarm current.
7 amp max.stand-by without battery back-up.
1 amp with battery back-up including dedicated Aux. output.
For Canadian applications Stand-by with battery backup is limited to 0.45 amp.
2.5 amp max current per output.
One (1) auxiliary output rated at 1 amp (regulated, battery backed up).
0.45 amp for Canadian applications.
Any NAC can be configured as an Aux. output with or
without battery back-up (special application only).
When set as Aux. output, the output is not supervised.
Low power shutdown. Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
Special Features:
Programmable LCD display interface.
EOL resistor value is programmable by output.
Ethernet port interface for remote programmability and monitoring.
2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
Sync protocols include Potter, Gentex®, System Sensor® , and CooperWheelock®.
Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
Compatible with 12VDC or 24VDC fire panels.
Output loop supervision directed to input 1 or input 2.
Common trouble Dry N.C. output for reporting trouble to remote FACP.
Ground fault detection - Ground fault maximum test impedance 1,000 ohm.
Ground fault Dry N.O. output to report ground fault to remote FACP.
CO Temporal Code 4 (NFPA720) include Gentex® , Potter and System Sensor® devices.
Electrical:
Operating temperature: 0° C to 49° C ambient.
BTU/Hr.: 122.84BTU/Hr.
System AC input VA requirement: 576VA.
Visual Indicators:
LCD display - Indicates troubles and conditions of operation. Trouble Condition Memory facilitates quick identification of an intermittent/fault (short circuit, open or ground) which has previously occurred on one or more signaling circuit outputs.
LCD displays which output the fault has occurred on.
Managed NAC Power Extender 120 VAC 60HZ, 4.8 Amp Input
Product Type
Alarm Control Panel Expansion Module
Environmental Compliance
Restriction of Hazardous Substances (RoHS)
Device Supported
Control Panel
Environmentally Friendly
Yes
Country of Origin
United States
Height
15.5"
Width
12.3"
Depth
4.5"
Product Model
FIRESWITCH108
Input Voltage
24 V DC
Packaged Quantity
1
Limited Warranty
Lifetime
Minimum Operating Temperature
32°F (0°C)
Maximum Operating Temperature
120.2°F (49°C)